9.4 GOT Side Settings

9.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: RKC
• Controller Type: RKC SR Mini HG
• I/F: Interface to be used
• Driver: RKC SR Mini HG(MODBUS)
4.
The detailed setting is displayed after Manufacturer,
Controller Type,
I/F, and Driver are set.
Make the settings according to the usage
environment.
9.4.2Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3.
4.
Transmissio
n Speed
Data Bit
Click!
Stop Bit
Parity
Retry
Timeout
Time
Delay Time
Format
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.4.2
Communication detail settings
Item
Description
Set this item when change the transmission
speed used for communication with the
connected equipment.
(Default: 9600bps)
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 8bits)
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: No)
Set the number of retries to be performed when
a communication error occurs.
(Default: 0time)
Set the time period for a communication to time
out.
(Default: 3sec)
Set this item to adjust the transmission timing
of the communication request from the GOT.
(Default: 0ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to H-PCP-J, H-PCP-A, H-PCP-B,
SRZ, FB, PF, HA, MA, RMC, SRX, B400 series
Format 2:
Accessible to CB series, RB, AG, THV, SA, SB1
series
9.4 GOT Side Settings
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
9
None
Even
Odd
0 to 5times
3 to 30sec
0 to 300ms
1/2
9 - 39