Mitsubishi Electric GOT2000 Series Connection Manual page 125

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(7) RS-485 connection diagram 7)
GOT side
SDA
1
SDB
6
RDA
2
RDB
7
SG
5
RSA
3
CSA
4
RSB
8
CSB
9
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
Signal name
*2
Terminating resistor should be provided for a temperature controller which will be a terminal.
*3
Set the terminating resistor of GOT side which will be a terminal.
*4
Connect FG grounding to the appropriate part of a cable shield line.
Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) FUJI temperature controller side connector
Use the connector compatible with the FUJI
temperature controller side.
For details, refer to the user's manual of the FUJI
temperature controller.
Connecting terminating resistors
(1) GOT side
Set the terminating resistor setting switch of the GOT
main unit to "100 OHM".
For the procedure to set the terminating resistor, refer
to the following.
1.4.3 Terminating resistors of GOT
(2) FUJI temperature controller side
When connecting a FUJI temperature controller to the
GOT, a terminating resistor must be connected.
5.5 Temperature Controller Side Setting
Temperature
* 3
controller side
+ * 1
- * 1
* 4
Terminating resistor(100Ω 1/2W)
PXR3
PXR4
Pin No.
Pin No.
+
15
7
-
14
8
■ Connecting terminating resistors
5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
Temperature
controller side
* 4
* 2
Model of temperature controller
PXR5/9
PXG4
PXG5/9
Pin No.
Pin No.
Pin No.
1
7
1
2
8
2
5.3 Connection Diagram
+ * 1
- * 1
PXH9
Pin No.
14
16
5 - 11
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents