Plc Side Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

10.2.6 PLC Side Setting

POINT
POINT
POINT
ALLEN-BRADLEY PLC
For details of ALLEN-BRADLEY PLCs, refer to the
following manuals.
ALLEN-BRADLEY PLC user's Manual
Directly connecting to the CPU
Item
SLC500
Series
4800bps,
*1
9600bps,
Baud Rate
19200bps
Parity
EVEN
Control Line
Communication
DF1 HALF-DUPLEX SLAVE
Driver
Duplicate Packet
Detection
Station Address
Error Detection
BCC
*1
Set the Baud Rate according to the transmission speed
setting on the GOT side.
For the transmission speed setting on the GOT side, refer to
the following.
10.2.5 ■ Communication detail settings
*2
Set the Error Detection according to the sum check format
setting on the GOT side.
For the sum check format setting on the GOT side, refer to
the following.
10.2.5 ■ Communication detail settings
Setting details
Control/
MicroLogix
Compact/
1000/1200/
FlexLogix
1500 Series
Series
4800bps,
4800bps,
9600bps,
9600bps,
19200bps,
19200bps,
38400bps
38400bps
NONE
NONE
NO HANDSHAKING
DISABLE
0
*2
*2
BCC, CRC
BCC, CRC
Connecting to DH485 network via adapter
(1770-KF3) (Setting of Adapter)
Item
*1
Baud Rate
Parity
Flow Control
DF1 Device
Category
*2
Error Detection
DH-485 Baud Rate
Maximum Node
Address
DH-485 Node
Address
*1
Set the Baud Rate according to the transmission speed
setting on the GOT side.
For the transmission speed setting on the GOT side, refer to
the following.
10.2.5 ■ Communication detail settings
*2
Set the Error Detection according to the sum check format
setting on the GOT side.
For the sum check format setting on the GOT side, refer to
the following.
10.2.5 ■ Communication detail settings
*3
For the Maximum Node Address, set the same address as
the Maximum Node Address on the DH-485 network.
*4
Set the DH-485 Node Address according to the Host
Address on the GOT side.
Set a unique DH-485 Node Address so that it does not
conflict with the Node Address of the PLC CPU on the DH-
485 network.
For the Host Address setting on the GOT side, refer to the
following.
10.2.5 ■ Communication detail settings
10. CONNECTION TO ALLEN-BRADLEY PLC
10.2 Serial Connection
Setting details
4800bps, 9600bps, 19200bps
Even
Disable (No Handshaking)
DF1 half-duplex slave, local mode
BCC
19200bps
*3
1 to 31
*4
0 to 31
10 - 13
10