1MRK 511 423-UEN A
Bay control REC650 2.2 IEC
Application manual
(WA1)A1
(WA2)B1
(WA7)C
BB_ES
ABC_LINE
IEC04000505 V1 EN-US
Figure 76:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnector on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay containing the above information.
These signals from each line bay (ABC_LINE), each transformer bay
(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:
Signal
QB1OPTR
QB1 is open.
QB2OPTR
QB2 is open (AB_TRAFO, ABC_LINE)
QB220OTR
QB2 and QB20 are open (ABC_BC)
QB7OPTR
QB7 is open.
VPQB1TR
The switch status of QB1 is valid.
VPQB2TR
The switch status of QB2 is valid.
VQB220TR
The switch status of QB2and QB20 is valid.
VPQB7TR
The switch status of QB7 is valid.
EXDU_BB
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnectors A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and
EXDU_DC are set to 1 (TRUE).
Section 1
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
AB_TRAFO ABC_LINE
Section 8
Control
Section 2
A2
B2
C
BB_ES
en04000505.vsd
153