Section 13
Station communication
248
Using PTP for synchronizing the MU
SAM600 VT
IEC17000040 V1 EN-US
Figure 118:
Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc: is not used as the SW-time and HW-time are connected with each
other due to PTP
SyncLostMode : set to Block to block protection functions if time
synchronization is lost or set to BlockOnLostUTC if the protection functions
are to be blocked when global common synchronization is lost
SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase
angle error of 0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X:
Operation: On
PTP: On
IED
9-2
PTP
SAM600 TS
SAM600 CT
IEC17000040-1-en.vsdx
1MRK 511 423-UEN A
Bay control REC650 2.2 IEC
Application manual