Interlocking For Transformer Bay Ab_Trafo; Application - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 423-UEN A
8.3.4
8.3.4.1
Bay control REC650 2.2 IEC
Application manual
BC_12_CL = 0
VP_BC_12 = 1
BBTR_OP = 1
VP_BBTR = 1

Interlocking for transformer bay AB_TRAFO

Application

The interlocking for transformer bay (AB_TRAFO) function is used for a
transformer bay connected to a double busbar arrangement according to figure 57.
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be
used. This function can also be used in single busbar arrangements.
QB1
QB2
QC1
QA1
QC2
T
QC3
QA2
QC4
QB3
QB4
IEC04000515 V1 EN-US
Figure 57:
Switchyard layout AB_TRAFO
The signals from other bays connected to the module AB_TRAFO are described
below.
WA1 (A)
WA2 (B)
AB_TRAFO
QA2 and QC4 are not
used in this interlocking
en04000515.vsd
Section 8
Control
IP14149-1 v2
M13567-3 v7
M13566-4 v4
139