Setting Example - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 9
Logic
9.14.4
192
EqualBandHigh: This setting is used to set the equal condition high band limit in %
of reference value. This high band limit will act as reset limit for INHIGH output
when INHIGH.
EqualBandLow: This setting is used to set the equal condition low band limit in %
of reference value. This low band limit will act as reset limit for INLOW output
when INLOW.

Setting example

Let us consider a comparison is to be done between current magnitudes in the
range of 90 to 110 with nominal rating is 100 and the order is kA.
For the above condition the comparator can be designed with settings as follows,
EnaAbs = Absolute
RefSource = Set Value
SetValue = 100
RefPrefix = Kilo
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value
Operation
The function will set the outputs for the following conditions,
INEQUAL will set when the INPUT is between the ranges of 95 to 105 kA.
INHIGH will set when the INPUT crosses above 105 kA.
INLOW will set when the INPUT crosses below 95 kA.
If the comparison should be done between two current magnitudes then those
current signals need to be connected to function inputs, INPUT and REF. Then the
settings should be adjusted as below,
EnaAbs = Absolute
RefSource = Input REF
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value.
1MRK 511 423-UEN A
GUID-E7070CF6-B44B-4799-BE18-5C75B9FE2A87 v2
Bay control REC650 2.2 IEC
Application manual