Bay control REC650 2.2 IEC
Application manual
Setting examples
Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
•
Measurement function (CVMMXN) application for a OHL
•
Measurement function (CVMMXN) application on the secondary side of a
transformer
•
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters
values will be provided.
The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in
PCM600.
Measurement function application for a 400kV OHL
Single line diagram for this application is given in figure 98:
400kV Busbar
1000/1 A
400
0
1 ,
/
kV
3
3
P
Q
400kV OHL
IEC09000039-1-EN V3 EN-US
Figure 98:
Single line diagram for 400kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as
indicated in figure
98
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef (see Section
PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
IED
IEC09000039-3-en.vsdx
"Setting of the phase reference
Section 10
Monitoring
SEMOD54481-4 v5
SEMOD54481-12 v11
channel") using
199