Bay control REC650 2.2 IEC
Application manual
Table 23:
General settings parameters for the Measurement function
Setting
Short description
Operation
Operation
PowAmpFact
Amplitude factor to scale power
calculations
PowAngComp
Angle compensation for phase
shift between measured I & U
Mode
Selection of measured current
and voltage
k
Low pass filter coefficient for
power measurement, U and I
UGenZeroDb
Zero point clamping in % of
Ubase
IGenZeroDb
Zero point clamping in % of
Ibase
UBase (set in
Base setting for voltage level in
Global base)
kV
IBase (set in
Base setting for current level in
Global base)
A
SBase (set in
Base setting for power in MVA
Global base)

Gas medium supervision SSIMG

Identification

Function description
Insulation gas monitoring function

Application

Gas medium supervision (SSIMG) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation shall be blocked to minimize the risk of internal failure.
Binary information based on the gas pressure in the circuit breaker is used as an
Selected
value
Off / On
On
1.000
180.0
L1L2
0.00
25
3
35.00
495
31.5
IEC 61850
identification
SSIMG
Section 10
Monitoring
Comment
On
Function must be
Typically no scaling is required
Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Only UL1L2 phase-to-phase
voltage is available
Typically no additional filtering is
required
Set minimum voltage level to
25%
Set minimum current level to 3%
Set LV side rated phase-to-
phase voltage
Set transformer LV winding rated
current
Set based on rated power
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
203

Advertisement

Table of Contents
loading

This manual is also suitable for:

RelionRec650

Table of Contents