Specific Settings Related To The Iec/Uca 61850-9-2Le; Communication; Loss Of Communication When Used With Ldcm - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 13
Station communication
13.3.2.1
13.3.2.2
242
Main menu/Configuration/Analog modules/MUx:92xx. The corresponding
settings are also available in PST (PCM600).
Main menu/Configuration/Communication/Merging units configuration/
MUx:92xx. The corresponding settings are also available in ECT (PCM600).
Xx can take value 1–4.

Specific settings related to the IEC/UCA 61850-9-2LE

communication

The process bus communication IEC/UCA 61850-9-2LE has specific settings,
similar to the analog inputs modules.
If there are more than one sample group involved, time synch is mandatory. If there
is no time synchronization, the protection functions will be blocked due to
condition blocking.
CTStarPointx: These parameters specify the direction to or from object. See also
section
"Setting of current
SyncLostMode: If this parameter is set to Block and the IED hardware time
synchronization is lost or the synchronization to the MU time is lost, the protection
functions in the list
24
will be blocked due to conditional blocking. If this
parameter is set to BlockOnLostUTC, the protection functions in list
if the IED hardware time synchronization is lost or the synchronization of the MU
time is lost or the IED has lost global common synchronization (i.e. GPS, IRIG-B
or PTP). SYNCH output will be set if IED hardware time synchronization is lost.
MUSYNCH output will be set if either of MU or IED hardware time
synchronization is lost.

Loss of communication when used with LDCM

If IEC/UCA 61850-9-2LE communication is lost, see examples in figures 115,
and 117, the protection functions in table
degradation.
Case 1:
channels".
24
are blocked as per graceful
1MRK 511 423-UEN A
SEMOD166590-24 v6
24
are blocked
GUID-29EFBCB7-2B4F-4AA1-B593-8E89838722E0 v3