ABB 650 series Applications Manual page 246

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 13
Station communication
240
IEC06000537 V1 EN-US
Figure 113:
Example of a station configuration with separated process bus and
station bus
The IED can get analog values simultaneously from a classical CT or VT and from
a Merging Unit, like in this example:
The merging units (MU) are called so because they can gather analog values from
one or more measuring transformers, sample the data and send the data over
process bus to other clients (or subscribers) in the system. Some merging units are
able to get data from classical measuring transformers, others from non-
conventional measuring transducers and yet others can pick up data from both
types. The electronic part of a non-conventional measuring transducer (like a
Rogowski coil or a capacitive divider) can represent a MU by itself as long as it
can send sampled data over process bus.
1MRK 511 423-UEN A
Bay control REC650 2.2 IEC
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

RelionRec650

Table of Contents