Received Goose Interlocking Information Goosercv_Intl - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.18.6
Received GOOSE interlocking information
GOOSERCV_INTL
3.18.6.1
Function block
Figure 99: Function block
3.18.6.2
Functionality
The received GOOSE interlocking information function GOOSERCV_INTL is used to
connect the GOOSE double binary input to the application and extracting single
binary position signals from the double binary position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
3.18.6.3
Signals
Table 149: GOOSERCV_INTL Input signals
Name
IN
Table 150: GOOSERCV_INTL Output signals
Name
OP
CL
OK
VALID
REX640
Technical Manual
Type
Default
Dbpos
0
Type
Description
BOOLEAN
Position open output signal
BOOLEAN
Position closed output signal
BOOLEAN
Position OK output signal
BOOLEAN
Output signal
Basic functions
Description
Input signal
211