16 Settable Real Values Setrgapc - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.20.10.4
Signals
Table 240: SCA4GAPC Input signals
Name
AI1_VALUE
AI2_VALUE
AI3_VALUE
AI4_VALUE
Table 241: SCA4GAPC Output signals
Name
AO1_VALUE
AO2_VALUE
AO3_VALUE
AO4_VALUE
3.20.10.5
Settings
Table 242: SCA4GAPC settings
Parameter
Values (Range)
Scale ratio 1
0.001...1000.000
Scale ratio 2
0.001...1000.000
Scale ratio 3
0.001...1000.000
Scale ratio 4
0.001...1000.000
3.20.11

16 settable real values SETRGAPC

3.20.11.1
Identification
Function description
16 settable real values
REX640
Technical Manual
If the result of AIn_VALUE multiplied by the Scale ratio n setting exceeds
the analog output range, AOn_VALUE shows the minimum or maximum
value, according to analog value range.
Type
FLOAT32
FLOAT32
FLOAT32
FLOAT32
Type
FLOAT32
FLOAT32
FLOAT32
FLOAT32
Unit
Step
0.001
0.001
0.001
0.001
Default
0.0
0.0
0.0
0.0
Description
Analog value 1 after scaling
Analog value 2 after scaling
Analog value 3 after scaling
Analog value 4 after scaling
Default
1.000
1.000
1.000
1.000
IEC 61850
IEC 60617
identification
identification
SETRGAPC
SETRGAPC
Basic functions
Description
Analog input value of
channel 1
Analog input value of
channel 2
Analog input value of
channel 3
Analog input value of
channel 4
Description
Scale ratio for analog value 1
Scale ratio for analog value 2
Scale ratio for analog value 3
Scale ratio for analog value 4
ANSI/IEEE C37.2
device number
SETRGAPC