1MRS759142 F
ILTCTR Output signals
Table 119: ILTCTR Output signals
Name
ALARM
WARNING
I3P
IRES_CLC
IRES_CLC_DR
IL1_DR
IL2_DR
IL3_DR
NPS_DR
PPS_DR
3.17.1.5
Settings
ILTCTR Settings
Table 120: ILTCTR Non group settings (Basic)
Parameter
Values (Range)
Current input type
2=Current trafo
4=Current sensor
Primary current
1.0...15000.0
Secondary current
2=1A
3=5A
Rated secondary
1.000...150.000
Val
Amplitude Corr A
0.9000...1.1000
Amplitude Corr B
0.9000...1.1000
Amplitude Corr C
0.9000...1.1000
Angle Corr A
-8.0000...8.0000
Angle Corr B
-8.0000...8.0000
Angle Corr C
-8.0000...8.0000
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
Unit
Step
A
0.1
mV/Hz
0.001
0.0001
0.0001
0.0001
deg
0.0001
deg
0.0001
deg
0.0001
Basic functions
Description
Alarm
Warning
Three-phase currents
Residual current, calculated
Residual current, calculated,
for disturbance recorder
Phase current IL1 for disturb-
ance recorder
Phase current IL2 for disturb-
ance recorder
Phase current IL3 for disturb-
ance recorder
Negative sequence current
for disturbance recorder
Positive sequence current for
disturbance recorder
Default
Description
2=Current trafo
Type of the current
input
100.0
Rated primary cur-
rent
2=1A
Rated secondary
current
3.000
Rated Secondary
Value (RSV) ratio
1.0000
Phase A amplitude
correction factor
1.0000
Phase B amplitude
correction factor
1.0000
Phase C amplitude
correction factor
0.0000
Phase A angle cor-
rection factor
0.0000
Phase B angle cor-
rection factor
0.0000
Phase C angle cor-
rection factor
193