Stabilized And Instantaneous Differential Protection For Two-Winding; Transformers Tr2Ptdf (Ansi 87T) - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Characteristics
Operate time accuracy in definite
time mode
Operate time accuracy in inverse
time mode
Suppression of harmonics
4.3.2
Stabilized and instantaneous differential protection for
two-winding transformers TR2PTDF (ANSI 87T)
4.3.2.1
Identification
Function description
Stabilized and instantaneous differ-
ential protection for two-winding
transformers
4.3.2.2
Function block
Figure 386: Function block
4.3.2.3
Functionality
The stabilized and instantaneous differential protection for two-winding
transformers function TR2PTDF is designed to protect two-winding transformers
and generator-transformer blocks. TR2PTDF includes low biased and high
instantaneous stages.
The biased low stage provides a fast clearance of faults while remaining stable
with high currents passing through the protected zone increasing errors on current
measuring. The second harmonic restraint, together with the waveform based
algorithms, ensures that the low stage does not operate due to the transformer
inrush currents. The fifth harmonic restraint ensures that the low stage does not
operate on apparent differential current caused by a harmless transformer over-
excitation.
4
Low operate value multiples in the range of 1.5...20
680
Value
±1.0% of the set value or ±20 ms
±5.0% of the set value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Peak-to-Peak: No suppression
IEC 61850
IEC 60617
identification
identification
TR2PTDF
3dI>T
1MRS759142 F
4
ANSI/IEEE C37.2
device number
87T
REX640
Technical Manual