ABB RELION REX640 Technical Manual page 868

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.5.3.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of ROVPTOV can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 487: Functional module diagram
Level detector
The residual voltage is compared to the set
Start value , the level detector sends an enable signal to the timer.
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set by
delay time , the OPERATE output is activated. If the fault disappears before the
module operates, the reset timer is activated. If the reset timer reaches the
value set by
deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the BLOCK input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The BLOCK input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the BLOCK signal activation
is preselected with the global setting
The
mode, the operation timer is frozen to the prevailing value, but the OPERATE output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the OPERATE output is not activated.
868
U
O
URES
Blocking
BLOCK
Reset delay time , the operate timer resets and the START output is
Blocking mode setting has three blocking methods. In the "Freeze timers"
Timer
Level
t
detector
logic
Start value . If the value exceeds the set
Blocking mode .
1MRS759142 F
Operation setting. The
OPERATE
START
Operate
Technical Manual
REX640