Protection functions
Blocking inputs
BLOCK
BLK_OPR_LS
BLK_OPR_HS
4.3.3.6
Current transformer connections and transformation ratio
correction
The combinations of the connections of the primary current transformers are
designated as "Type 1" and "Type 2". The type needs to be selected separately
for the combination of CT connections on the winding 1 and 2 sides as well as
for the combination of CT connections on the winding 1 and 3 sides in case of
three-winding transformer.
• If the positive directions of the winding 1 and winding 2 relay currents are
opposite, the setting parameter
415
• If the positive directions of the winding 1 and winding 2 relay currents are equal,
the setting parameter
• 'The default value of the
• The same applies for the
730
.
CT connection 1-2 is "Type 2", as shown in
CT connection 1-2 settings is "Type 1".
Description
When active (TRUE), the operation of the function is blocked;
only measurement value outputs are updated.
When active (TRUE), TR3PTDF acts normally except that the
output is not active or activated in any circumstan-
OPR_LS
ces. Additionally, the
OPERATE
by the instantaneous high stage (if not blocked).
When active (TRUE), TR3PTDF acts normally except that the
output is not active or activated in any circumstan-
OPR_HS
ces. Additionally, the
OPERATE
by the biased low stage (if not blocked).
CT connection 1-2 is "Type 1", as shown in
CT connection 1-3 settings.
1MRS759142 F
output can be activated only
output can be activated only
Figure
Figure 416
.
REX640
Technical Manual