LREFPNDF does not respond to phase-to-phase faults either, as in this case the
fault current flows between the two line CTs and so the neutral CT does not
experience this fault current.
Blocking based on the second harmonic of the neutral current
The transformer magnetizing inrush currents occur when the transformer is
energized after a period of de-energization. The inrush current can be many times
the rated current, and the halving time can be up to several seconds. For the
differential protection relay, the inrush current represents the differential current,
which causes the protection relay to operate almost always when the transformer is
connected to the network. Typically, the inrush current contains a large amount of
second harmonics.
The blocking also prevents unwanted operation at the recovery and sympathetic
magnetizing inrushes. At the recovery inrush, the magnetizing current of the
transformer to be protected increases momentarily when the voltage returns to
normal after the clearance of a fault outside the protected area. The sympathetic
inrush is caused by the energization of a transformer running in parallel with the
protected transformer already connected to the network.
Blocking the starting of the restricted earth-fault protection at the magnetizing
inrush is based on the ratio of the second harmonic and the fundamental frequency
amplitudes of the neutral current Io_2H / Io. Typically, the second harmonic content
of the neutral current at the magnetizing inrush is higher than that of the phase
currents.
4.3.4.7
Signals
LREFPNDF Input signals
Table 680: LREFPNDF Input signals
Name
I3P
IRES
BLOCK
LREFPNDF Output signals
Table 681: LREFPNDF Output signals
Name
OPERATE
START
BLKD2H
REX640
Technical Manual
Type
Default
SIGNAL
-
SIGNAL
-
BOOLEAN
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
Protection functions
Description
Three-phase currents
Residual current
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
2nd harmonic block