1MRS759142 F
4.3.6.11
Technical data
Table 715: HIxPDIF Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
1
Measurement mode = default (depends on stage), current before fault = 0.0 × I
current with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements.
2
Measured with static signal output (SSO).
REX640
Technical Manual
1, 2
I
= 2.0 × set
Fault
value
I
= 10 × set
Fault
value
Value
Depending on the frequency of the current
measured: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
Minimum
Start
8 ms
Start
7 ms
Typically <40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Protection functions
n
Typical
Maximum
11 ms
19 ms
9 ms
11 ms
, f
= 50 Hz, fault
n
n
787