ABB RELION REX640 Technical Manual page 434

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
Relative starting
100.0...2000.0
current
Motor synchronous
125...3600
speed
Motor nominal
100...3599
speed
Table 492: RPTTR Non group settings (Advanced)
Parameter
Values (Range)
Current reference
0.30...2.00
Initial thermal Val
0.0...100.0
Slip Clc delay
10...2000
4.1.11.9
RPTTR Monitored data
Table 493: RPTTR Monitored data
Name
Type
TEMP_AMB
FLOAT32
THERMLEV_ST
FLOAT32
THERMLEV_END
FLOAT32
T_ENARESTART
INT32
I_REF_CLC
FLOAT32
RPTTR
Enum
Therm-Lev:1
FLOAT32
4.1.11.10
Technical data
Table 494: RPTTR Technical data
Characteristics
Operation accuracy
Operate time accuracy
434
Unit
Step
%Ir
0.1
1
1
Unit
Step
xIn
0.01
%
0.1
ms
1
Values (Range)
-99...999
0.00...9.99
0.00...9.99
0...99999
0.1...3.0
1=on
2=blocked
3=test
4=test/blocked
5=off
0.00...9.99
Value
Depending on the frequency of the measured current fn ±2 Hz
Current measurement ±1.5% of the set value or ±0.002 x I
currents in the range of ≤4.00 x I
±2.0% of the theoretical value or ±0.50 s
Default
600.0
1500
1485
Default
1.00
74.0
200
Unit
Description
°C
The ambient tempera-
ture used in the calcula-
tion
Thermal level at begin-
ning of motor startup
Thermal level at the end
of motor startup situa-
tion
s
Estimated time to reset
of block restart
Adjusted Rated current
(FLC) of the motor
Status
Thermal level of protec-
ted object (1.00 is the
operate level)
)
n
1MRS759142 F
Description
Relative starting
current i.e. locked
rotor current
Motor synchronous
speed in rpm
Motor speed at
nominal load in
rpm
Description
Rated current (FLC)
of the motor
Initial thermal level
of the rotor
Delay before slip
estimate calcula-
tion starts
(at
n
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents