1MRS759142 F
The fault-related current, voltage, frequency, angle values, shot pointer and the
active setting group number are taken from the moment of the operate event, or
from the beginning of the fault if only a start event occurs during the fault. The
maximum current value collects the maximum fault currents during the fault. If
frequency cannot be measured, nominal frequency is used for frequency and zero
for frequency gradient and validity is set accordingly.
The measuring mode for phase current and residual current values can be selected
with the
3.9.3

Analog channel configuration

FLTRFRC has twelve analog group inputs which must be properly configured. All
inputs can be connected to GRPOFF.
Table 84: Analog inputs
Input
I3P1
I3P2
I3P3
IRES1
IRES2
IRES3
U3P1
U3P2
U3P3
URES1
URES2
URES3
There are a few special conditions which must be noted with the configuration.
1
Can be connected to GRPOFF
REX640
Technical Manual
A measurement mode setting parameter.
For a detailed description of the measurement modes, see
Measurement modes
1
1
1
1
1
1
1
1
1
1
1
1
See the preprocessing function blocks in this document for the possible
signal sources. The GRPOFF signal is available in the function block called
Protection.
in this manual.
Description
Three-phase currents
Three-phase currents
Three-phase currents
Residual current (measured or calculated)
Residual current (measured or calculated)
Residual current (measured or calculated)
Three-phase voltages
Three-phase voltages
Three-phase voltages
Residual voltage (measured or calculated)
Residual voltage (measured or calculated)
Residual voltage (measured or calculated)
Basic functions
Chapter 11.6
145