Protection functions
OEPVPH Output signals
Table 845: OEPVPH Output signals
Name
OPERATE
START
BLK_RESTART
COOL_ACTIVE
4.5.7.9
OEPVPH Settings
Table 846: OEPVPH Group settings (Basic)
Parameter
Values (Range)
Start value
100...200
Operating curve
5=ANSI Def. Time
type
15=IEC Def. Time
17=OvExt IDMT Crv1
18=OvExt IDMT
Crv2
19=OvExt IDMT
Crv3
20=OvExt IDMT
Crv4
Time multiplier
0.1...100.0
Operate delay time
200...200000
Table 847: OEPVPH Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Cooling time
5...10000
Constant delay
100...120000
Maximum operate
500000...10000000 ms
time
Voltage selection
1=phase-to-earth
2=phase-to-phase
3=pos sequence
Phase selection
1=A or AB
2=B or BC
3=C or CA
Table continues on the next page
898
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
%
1
0.1
ms
10
Unit
Step
s
1
ms
10
10
1MRS759142 F
Description
Operated
Started
Signal for blocking reconnec-
tion of an overheated ma-
chine
Signal to indicate machine is
in cooling process
Default
Description
100
Over excitation
start value
15=IEC Def. Time
Selection of time
delay curve type
3.0
Time multiplier
for Overexcitation
IDMT curves
500
Operate delay time
in definite- time
mode
Default
Description
1=on
Operation Mode
Off / On
600
Time required to
cool the machine
800
Parameter constant
delay
1000000
Maximum operate
time for IDMT
curves
3=pos sequence
Selection of
phase / phase-to-
phase / pos se-
quence voltages
1=A or AB
Parameter for
phase selection
Technical Manual
REX640