1MRS759142 F
Figure 242: Trip curves at prior load 1 x FLC and p=50 %. Overload factor = 1.05.
4.1.10.6
Application
MPTTR is intended to limit the motor thermal level to predetermined values
during the abnormal motor operating conditions. This prevents a premature motor
insulation failure.
The abnormal conditions result in overheating and include overload, stalling, failure
to start, high ambient temperature, restricted motor ventilation, reduced speed
operation, frequent starting or jogging, high or low line voltage or frequency,
mechanical failure of the driven load, improper installation and unbalanced
line voltage or single phasing. The protection of insulation failure by the
implementation of current sensing cannot detect some of these conditions, such
as restricted ventilation. Similarly, the protection by sensing temperature alone
can be inadequate in cases like frequent starting or jogging. The thermal overload
REX640
Technical Manual