Smv Stream Receiver (Iec 61850-9-2Le) Smvrcv - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
3.16.2

SMV stream receiver (IEC 61850-9-2LE) SMVRCV

3.16.2.1
Function block
Figure 87: Function block
3.16.2.2
Functionality
The SMV stream receiver (IEC 61850-9-2LE) function SMVRCV is used for connecting
SMV channels to the application.
3.16.2.3
Signals
Table 116: SMVRCV Output signals
Name
UL1
UL2
UL3
U0
IL1
IL2
IL3
I0
190
Type
Description
INT32-UL1
IEC61850-9-2 phase 1 voltage
INT32-UL2
IEC61850-9-2 phase 2 voltage
INT32-UL3
IEC61850-9-2 phase 3 voltage
INT32-Uo
IEC61850-9-2 residual voltage
INT32-IL1
IEC61850-9-2 phase 1 current
INT32-IL2
IEC61850-9-2 phase 2 current
INT32-IL3
IEC61850-9-2 phase 3 current
INT32-I0
IEC61850-9-2 residual current
1MRS759142 F