1MRS759142 F
The RTD inputs have separate setting values for value update interval. The settings
are: "No delay", "10 ms delay", "50 ms delay" and "100 ms delay". Between the update
intervals the RTD input constantly returns the last valid value before updating to the
new value after the interval time expires.
3.15.3.1
Input mode
Table 100: Analog input modes for the mA inputs
Input mode
Not in use
–20...20 mA
Table 101: Analog input modes for the RTD inputs
Input mode
Not in use
Resistance
Pt 100
Pt 250
Ni 100
Ni 120
Ni 250
Selection of value unit format
Each input has an independent
for the channel value representation. The default value for the
"Dimensionless". The
minimum settings have to be adjusted according to the input channel and if Value
unit is changed.
When the RTD channel input is used for the temperature sensor type, the
unit setting needs to be changed to "Degrees Celsius". When Value unit is set to
"Degrees Celsius", linear scaling is not applied but the default range (–40...200°C)
can be decreased with the
When the DC milliampere signal is connected to the mA channel and the application
requires a linear scaling of the input range, the
to "Dimensionless" so that the input range can be linearly scaled with the settings
Input minimum and Input maximum to
milliampere is used as a value unit,
is set to "Ampere", the default range (–20...20 mA) can be decreased with the
maximum and Value minimum settings.
REX640
Technical Manual
Description
Default selection when the corresponding input is not used.
The analog input covers the range of –20...20 mA. The input
can be used in a narrower range by setting
and
Input maximum . Settings Value minimum and Value
maximum are used to scale the output within the appropri-
ate range. The output unit is selected with the set
Description
Default selection when the corresponding input is not used.
Freely settable resistance input.
maximum define the resistive input range. The correspond-
ing output can be scaled based on
maximum . The output unit is selected with the set Value
unit .
The input is expected to be the selected temperature sensor.
Value unit should be set to degrees Celsius. The
The set
expected input range is –40...200°C. However, the output can
be scaled to a narrower output range by setting
mum and Value maximum .
Value unit setting that is used to select the unit
Input minimum , Input maximum , Value maximum and Value
Value maximum and Value minimum settings.
Value minimum and Value maximum . When
Value unit has to be "Ampere". When Value unit
Input minimum
Input minimum and Input
Value minimum and Value
Value unit setting is
Value unit setting value has to be set
Basic functions
Value unit .
Value mini-
Value
Value
171