ABB RELION REX640 Technical Manual page 280

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Depending on the connected I3P channels to the current switch, the
current settings between the source I3P must match. Depending on the connected
IRES channels, the
match. Setting validation for the primary current fails unless they are all stored
simultaneously to the protection relay.
3.20.17.6
Signals
Table 267: CMSWI Input signals
Name
I3P1
I3P2
I3P3
I3P4
IRES1
IRES2
IRES3
IRES4
SWITCH_TO2
SWITCH_TO3
SWITCH_TO4
Table 268: CMSWI Output signals
Name
SOURCE1
SOURCE2
SOURCE3
SOURCE4
I3P
IRES
ALARM
WARNING
3.20.17.7
CMSWI Monitored data
Table 269: CMSWI Monitored data
Name
SWITCH_POS
280
Primary current settings between the source IRES must
Type
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
Type
Values (Range)
Enum
1=Source 1
2=Source 2
Default
Description
-
Three-phase currents
1
-
Three-phase currents
2
-
Three-phase currents
3
-
Three-phase currents
4
-
Residual current 1
-
Residual current 2
-
Residual current 3
-
Residual current 4
0=False
Switch to source 2
0=False
Switch to source 3
0=False
Switch to source 4
Description
Selected current source is source 1
Selected current source is source 2
Selected current source is source 3
Selected current source is source 4
Three-phase currents
Residual current
Alarm
Warning
Unit
1MRS759142 F
Primary
Description
Switch position
REX640
Technical Manual