ABB RELION REX640 Technical Manual page 743

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
TR3PTDF Output signals
Table 672: TR3PTDF Output signals
Name
OPERATE
OPR_LS
OPR_HS
BLKD2H
BLKD5H
BLKDWAV
4.3.3.10
TR3PTDF Settings
Table 673: TR3PTDF Group settings (Basic)
Parameter
Values (Range)
High operate value
500...3000
Enable high set
0=False
1=True
Low operate value
5...50
Slope section 2
10...50
End section 2
100...500
Restraint mode
5=Waveform
6=2.h + waveform
8=5.h + waveform
9=2.h + 5.h + wav
Start value 2.H
7...20
Start value 5.H
10...50
Stop value 5.H
10...50
Harmonic deblock
0=False
2.
1=True
Harmonic deblock
0=False
5.
1=True
Table 674: TR3PTDF Group settings (Advanced)
Parameter
Values (Range)
Slope section 3
10...100
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
%Ir
10
%Ir
1
%
1
%Ir
1
%
1
%
1
%
1
Unit
Step
%
1
Protection functions
Description
Operate combined
Operate from low set
Operate from high set
2nd harmonic restraint block
status
5th harmonic restraint block
status
Waveform blocking status
Default
Description
1000
Instantaneous
stage setting
1=True
Enable high set
stage
20
Basic setting for
biased operation
30
Slope of the second
line of the operat-
ing characteristics
150
Turn-point between
the second and the
third line of the op-
erating characteris-
tics
9=2.h + 5.h + wav
Restraint mode
15
2. harmonic block-
ing ratio
35
5. harmonic block-
ing ratio
35
5. harmonic de-
blocking ratio
1=True
2. harmonic de-
blocking in case of
switch on to fault
0=False
5. harmonic de-
blocking in case of
severe overvoltage
Default
Description
100
Slope of the third
line of the operat-
ing characteristics
743