ABB RELION REX640 Technical Manual page 994

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
5=off
Phase voltage Meas 1=Accurate
2=Ph-to-ph without
Uo
Select active zones
1=Zone 1
2=Zones 1-2
3=Zones 1-3
4=Zones 1-4
5=All 5 zones
System grounding
1=High impedance
GFC
2=Low impedance
3=From input
Ph Prf mode Lo Z
1=All loops
GFC
2=PE only
3=PP only
4=BLK leading PE
5=BLK lagging PE
Ph Prf mode Hi Z
1=No filter
GFC
2=No preference
3=Cyc A-B-C-A
4=Cyc A-C-B-A
5=Acyc A-B-C
6=Acyc A-C-B
7=Acyc B-A-C
8=Acyc B-C-A
9=Acyc C-A-B
10=Acyc C-B-A
Impedance mode
1=Rectangular
Zn
2=Polar
Impedance Chr Gnd
1=Quadrilateral
Zn
2=Mho (circular)
3=Mho Dir line
4=Offset Dir line
5=Bullet (combi)
Impedance Chr PP
1=Quadrilateral
Zn
2=Mho (circular)
3=Mho Dir line
4=Offset Dir line
5=Bullet (combi)
Pol quantity zone
5=Cross pol
7=Pos. seq. volt.
1=Self pol
Max phase angle
0...60
zone
Min phase angle
90...150
zone
994
Unit
Step
deg
1
deg
1
1MRS759142 F
Default
Description
1=Accurate
Phase voltage
measurement prin-
ciple
1=Zone 1
Active zones selec-
tion
2=Low impedance
Network neutral
earthing method
1=All loops
Loop selection
mode for low impe-
dance earthed net-
work
1=No filter
Phase preference
mode for high im-
pedance earthed
network
1=Rectangular
Impedance charac-
teristic, underimpe-
dance, PSL
1=Quadrilateral
Impedance charac-
teristic for PE-
loops, zones
1=Quadrilateral
Impedance charac-
teristic for PP/3P-
loops, zones
7=Pos. seq. volt.
Mho polarization
method for zones
15
Angle from R-axis
to right hand side
directional line
115
Angle from R-axis
to left hand side di-
rectional line
Technical Manual
REX640