1MRS759142 F
Parameter
Values (Range)
3=Reverse
Voltage start value
0.01...1.00
Operate delay time
60...1200000
Table 620: MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Operating quantity 1=Adaptive
2=Amplitude
3=Resistive
Min operate current 0.005...5.000
Tilt angle
2.0...20.0
Table 621: MFADPSDE Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Operation mode
1=Intermittent EF
2=Transient EF
3=General EF
4=Alarming EF
Table 622: MFADPSDE Non group settings (Advanced)
Parameter
Values (Range)
Peak counter limit
2...20
Start delay time
30...60000
Reset delay time
0...60000
Pol reversal
0=False
1=True
4.2.9.9
MFADPSDE Monitored data
Table 623: MFADPSDE Monitored data
Name
Type
START_DUR
FLOAT32
ANGLE
FLOAT32
I_OPER
FLOAT32
MFADPSDE
Enum
REX640
Technical Manual
Unit
Step
xUn
0.01
ms
10
Unit
Step
xIn
0.001
deg
0.1
Unit
Step
Unit
Step
1
ms
1
ms
1
Values (Range)
0.00...100.00
-180.00...180.00
0.000...40.000
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Default
0.10
500
Default
1=Adaptive
0.010
5.0
Default
1=on
3=General EF
Default
2
30
500
0=False
Unit
Description
%
Ratio of start time / op-
erate time
deg
Angle between polar-
izing and operating
quantity
xIn
Calculated operating
current
Status
Description
Voltage start value
Operate delay time
Description
Operating quantity
selection
Minimum operate
current
Characteristic tilt
angle
Description
Operation Off / On
Operation criteria
Description
Peak counter limit
for restriking EF
Start delay time
Reset delay time
Rotate polarizing
quantity
581

Advertisement

Table of Contents
loading

Table of Contents