1MRS759142 F
Figure 11: High-availability seamless redundancy solution
3.2.3.1
Interlink port
In the relay redundant COM module, the port without LAN-A/LAN-B tag is so called
interlink-port. This port can be used to connect a device directly to the relay. Mainly
this port should be used to connect a single point-to-point device, such as RIO600.
Although it is possible, it not recommended to connect big amount of devices
behind the interlink port, thus making the relay act as a hub between two network
segments. The relay should preferrably act as a network end-device, and not as a
hub for network traffic.
3.2.4

Process bus

Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Values
within the substation automation system. International Users Group created a
guideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2
to facilitate implementation and enable interoperability. Process bus is used for
distributing process data from the primary circuit to all process bus compatible
devices in the local network in a real-time manner. The data can then be processed
by any protection relay to perform different protection, automation and control
functions.
Redundant SMV streams are also supported by using the voltage (VMSWI) and
current (CMSWI) function blocks. Automatic switching to the backup SMV stream
can be configured in Application Configuration using SMV quality and/or other
logic.
UniGear Digital switchgear concept relies on the process bus together with current
and voltage sensors. The process bus enables several advantages for the UniGear
Digital like simplicity with reduced wiring, flexibility with data availability to all
devices, improved diagnostics and longer maintenance cycles.
With process bus the galvanic interpanel wiring for sharing busbar voltage value
can be replaced with Ethernet communication. Transmitting measurement samples
REX640
Technical Manual
Redundancy
Redundancy
Box
Box
Redundancy
Redundancy
Box
Box
Basic functions
Redundancy
Redundancy
Box
Box
83