Protection functions
the voltage of the faulty phase decreases and the corresponding capacitance is
discharged to earth (→ discharge transients). At the same time, the voltages of
the healthy phases increase and the related capacitances are charged (→ charge
transient).
If the fault is permanent (non-transient) in nature, only the initial fault transient
in current and voltage can be measured, whereas the intermittent fault creates
repetitive transients.
Figure 277: Example of earth-fault transients, including discharge and charge
transient components, when a permanent fault occurs in a 20 kV network in phase C
4.2.3.7
Signals
INTRPTEF Input signals
Table 557: INTRPTEF Input signals
Name
IRES
URES
BLOCK
INTRPTEF Output signals
Table 558: INTRPTEF Output signals
Name
OPERATE
START
BLK_EF
488
Type
Default
SIGNAL
-
SIGNAL
-
BOOLEAN
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
1MRS759142 F
Description
Residual current
Residual voltage
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Block signal for EF to indicate
opposite direction peaks
REX640
Technical Manual