ABB RELION REX640 Technical Manual page 831

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
2=Forward
3=Reverse
Operate delay time
40...300000
Characteristic an-
-179...180
gle
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Table 749: DNSPDOC Group settings (Advanced)
Parameter
Values (Range)
Operating quantity 1=Negative seq
2=Residual
Table 750: DNSPDOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 751: DNSPDOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Allow Non Dir
0=False
1=True
Min operate current 0.01...1.00
Min operate volt-
0.01...1.00
age
4.4.2.10
DNSPDOC Monitored data
Table 752: DNSPDOC Monitored data
Name
Type
START_DUR
FLOAT32
FAULT_DIR
Enum
DIRECTION
Enum
Table continues on the next page
REX640
Technical Manual
Unit
Step
ms
10
deg
1
deg
1
deg
1
deg
1
deg
1
Unit
Step
Unit
Step
Unit
Step
ms
1
xIn
0.01
xUn
0.01
Values (Range)
0.00...100.00
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
Protection functions
Default
40
60
80
80
80
80
Default
1=Negative seq
Default
1=on
Default
20
0=False
0.01
0.01
Unit
Description
%
Ratio of start time / op-
erate time
Detected fault direction
Direction information
Description
Operate delay time
Characteristic an-
gle
Maximum phase
angle in forward di-
rection
Maximum phase
angle in reverse di-
rection
Minimum phase an-
gle in forward di-
rection
Minimum phase an-
gle in reverse direc-
tion
Description
Operating quantity
Description
Operation Off / On
Description
Reset delay time
Allows prot activa-
tion as non-dir
when dir info is in-
valid
Minimum operating
current
Minimum operating
voltage
831