ABB RELION REX640 Technical Manual page 485

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Figure 274: Example of INTRPTEF operation in "Transient EF" mode in the faulty
feeder
In the "Intermittent EF" mode the OPERATE output is activated when the following
conditions are fulfilled:
• the number of transients that have been detected exceeds the
setting
• the timer has reached the time set with the
• and one additional transient is detected during the drop-off cycle
The
there is no OPERATE activation, for example, the fault disappears momentarily
START stays activated until the
if time between transients is more than
a fixed pulse length of 100 ms for OPERATE is given, whereas START is reset after
Reset delay time elapses
REX640
Technical Manual
Reset delay time starts to elapse from each detected transient (peak). In case
Operate delay time
Reset delay time elapses, that is, reset takes place
Reset delay time . After OPERATE activation,
Protection functions
Peak counter limit
485