ABB RELION REX640 Technical Manual page 101

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
On the WHMI, internal fault information is shown under Self-Supervision Status.
Figure 28: Internal fault information on Web HMI
Table 43: Internal fault indications and codes
Fault
Fault indication
code
Internal Fault
2
System error
Internal Fault
2
System error
Internal Fault
2
System error
Internal Fault
2
System error
Internal Fault
2
System error
Internal Fault
2
System error
Internal Fault
2
System error
Table continues on the next page
REX640
Technical Manual
Fast self-
Additional
recovery
information
attempt
Start up error:
No
HW/SW mismatch
Start up or runtime
Yes
error: Data bus er-
ror, CPU module
Start up error: SCL
No
file missing
Start up error:
No
Missing order num-
ber
Start up error:
Yes
FPGA HW error,
CPU module
Start up error:
Yes
FPGA image cor-
rupted, CPU mod-
ule
Runtime error: CPU
Yes
internal fault
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
No
Yes
Yes (3)
No
No
Yes
No
Yes
Yes (3)
No
Yes (3)
No
Yes (3)
No
Basic functions
Action in permanent fault
state
If relay SW has just been
updated, redo it. If not re-
covered, contact your near-
est ABB representative to
check the next possible
corrective action.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Do factory restore or re-
write configuration using
PCM600.
Do factory restore. If not
recovered, contact your
nearest ABB representative
to check the next possible
corrective action.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Restart the relay or if relay
SW has just been updated,
redo it. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
ered by restarting or redo-
ing SW update, replace the
relay, most probably hard-
ware failure in CPU module.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
101