ABB RELION REX640 Technical Manual page 178

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
linear curves. The knee points are defined by parameters
Value knee point 1-4 .
Example 1: VMMXU1 to mA output
U3P
BLOCK
Figure 73: Application example for VMMXU1 to mA output
The measured phase-to-phase voltage from VMMXU is connected to
AO_VAL.
set to "18" (kV). The input unit is not significant as long as the value range is
in the same scale.
"4" mA.
Value maximum 20
Value minimum
Figure 74: Scaling of AO_VAL to mA output
Example 2: mA input to mA output
AO_VAL
AO_VAL
Figure 75: Application example for mA input to mA output
178
VMMXU1
HIGH_ALARM
HIGH_WARNING
LOW_WARN
LOW_ALARM
U12-kV
U23-kV
U31-kV
U_INST_A
U_INST_B
U_INST_C
Input maximum value is set to "24" (kV) and Input minimum value is
Value maximum is set to "20" mA and Value minimum to
Num of knee points is set to "0".
Output [mA]
12
4
18
Input minimum
Slot# – mA1
AI_VAL
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
Slot# – mA2
AI_VAL
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
Slot# – mA#
AO_VAL
AI_VAL
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
21
1MRS759142 F
Input knee point 1-4 and
AO_VAL
24
Input maximum
REX640
Technical Manual