Protection functions
LVRTPTUV Output signals
Table 855: LVRTPTUV Output signals
Name
OPERATE
START
4.5.8.8
LVRTPTUV Settings
Table 856: LVRTPTUV Group settings (Basic)
Parameter
Values (Range)
Voltage start value
0.05...1.20
Table 857: LVRTPTUV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Num of start pha-
4=Exactly 1 of 3
ses
5=Exactly 2 of 3
6=Exactly 3 of 3
Voltage selection
1=Highest Ph-to-E
2=Lowest Ph-to-E
3=Highest Ph-to-Ph
4=Lowest Ph-to-Ph
5=Positive Seq
Active coordinates
1...10
Voltage level 1
0.00...1.20
Voltage level 2
0.00...1.20
Voltage level 3
0.00...1.20
Voltage level 4
0.00...1.20
Voltage level 5
0.00...1.20
Voltage level 6
0.00...1.20
Voltage level 7
0.00...1.20
Voltage level 8
0.00...1.20
Table continues on the next page
906
Type
BOOLEAN
BOOLEAN
Unit
Step
xUn
0.01
Unit
Step
1
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
1MRS759142 F
Description
Operate
Start
Default
Description
0.90
Voltage value be-
low which function
starts
Default
Description
1=on
Operation Off / On
4=Exactly 1 of 3
Number of faulty
phases
4=Lowest Ph-to-Ph
Parameter to select
voltage for curve
monitoring
3
Coordinates used
for defining LVRT
curve
0.20
1st voltage coordi-
nate for defining
LVRT curve
0.80
2nd voltage coordi-
nate for defining
LVRT curve
0.90
3rd voltage coordi-
nate for defining
LVRT curve
0.90
4th voltage coordi-
nate for defining
LVRT curve
0.90
5th voltage coordi-
nate for defining
LVRT curve
0.90
6th voltage coordi-
nate for defining
LVRT curve
0.90
7th voltage coordi-
nate for defining
LVRT curve
0.90
8th voltage coordi-
nate for defining
LVRT curve