ABB RELION REX640 Technical Manual page 640

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
DT stage Op time
100...60000
IDMT stage Min Op
50...6000
Tm
IDMT stage Max Op
500...7200000
Tm
UTp multiplier
0.10...5.00
Reduction factor
0.10...1.00
Maximum earthing
0.5...1000.0
Ris
IEEE multiplier
50.0...5000.0
XC stage A Str Val
0.10...5.00
XC stage PP V Val
0.01...1.00
XC stage Op time
60...60000
Intr EF operate
100...10000
time
Table 640: IFPTOC Group settings (Advanced)
Parameter
Values (Range)
EF validity Op
1=Resistive
mode
2=Resistive, Reac-
tive
Table continues on the next page
640
Unit
Step
ms
10
ms
10
ms
10
0.01
0.01
ohm
0.1
0.1
xIn
0.01
xUn
0.01
ms
10
ms
10
Unit
Step
1MRS759142 F
Default
Description
500
Operate delay time
for Touch volt-
age/fault current
estimation module,
DT timer
100
Minimum operate
delay for touch
voltage/fault cur-
rent estimation
module IDMT tim-
er according to
standard EN50522/
IEEE80
10000
Maximum operate
delay for touch
voltage/fault cur-
rent estimation
module IDMT tim-
er according to
standard EN50522/
IEEE80
1.00
UTp multiplier for
IDMT curve accord-
ing to standard
EN50522
1.00
Reduction factor
in the touch volt-
age/fault current
estimation mod-
ule according to
standard EN50522/
IEEE80
10.0
Maximum earthing
resistance encoun-
tered in the protec-
ted feeder in pri-
mary ohms accord-
ing to standard
EN50522/IEEE80
157.0
Multiplier accord-
ing to standard
IEEE80
1.00
Current threshold
for cross-country
fault module. Note
that In means
phase nominal cur-
rent
0.90
Phase-to-phase
voltage threshold
for cross-country
fault detection
module. Note that
Un means phase to
phase nominal volt-
age.
200
Operate delay time
for cross-country
fault detection
stage
1000
Operate delay time
during intermittent
earth fault
Default
Description
2=Resistive, Reac-
EF validity opera-
tive
tion mode
Technical Manual
REX640