ABB RELION REX640 Technical Manual page 479

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
2=Def time reset
3=Inverse reset
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Enable voltage limit 0=False
1=True
Table 549: DEFHPDEF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 550: DEFHPDEF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum operate
40...60000
time
Allow Non Dir
0=False
1=True
Measurement
1=RMS
mode
2=DFT
3=Peak-to-Peak
Min operate current 0.5...100.0
Min operate volt-
1.00...100.00
age
Correction angle
0.0...10.0
Pol reversal
0=False
1=True
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
REX640
Technical Manual
Unit
Step
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
Unit
Step
ms
1
ms
1
%In
0.1
%Un
1.00
deg
0.1
Protection functions
Default
Description
1=Phase angle
Operation criteria
1=True
Enable voltage limit
Default
Description
1=on
Operation Off / On
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
29.10
Parameter D for
customer program-
mable curve
1.0
Parameter E for
customer program-
mable curve
Default
Description
20
Reset delay time
40
Minimum operate
time for IDMT
curves
0=False
Allows prot activa-
tion as non-dir
when dir info is in-
valid
2=DFT
Selects used meas-
urement mode
0.5
Minimum operating
current
1.00
Minimum operating
voltage
0.0
Characteristic cor-
rection angle in
IoCos and IoSin
mode
0=False
Rotate polarizing
quantity
3=Zero seq. volt.
Reference quantity
used to determine
fault direction
479