ABB RELION REX640 Technical Manual page 351

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.1.2.7
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area
is limited with the
operation area is limited with the
In the forward operation area, the
counterclockwise sector and the
clockwise sector, measured from the
In the backward operation area, the
counterclockwise sector and the
clockwise sector, a measurement from the
been rotated 180 degrees.
Figure 209: Configurable operating sectors
Table 393: Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The ANGLE_X is not in any of the defined sectors, or the direc-
tion cannot be defined due too low amplitude
The ANGLE_X is in the forward sector
Table continues on the next page
REX640
Technical Manual
Min forward angle and Max forward angle settings. The reverse
The sector limits are always given as positive degree values.
Min reverse angle and Max reverse angle settings.
Max forward angle setting gives the
Min forward angle setting gives the corresponding
Characteristic angle setting.
Max reverse angle setting gives the
Min reverse angle setting gives the corresponding
Characteristic angle setting that has
Protection functions
The value for DIR_A/_B/_C
0 = unknown
1 = forward
351