Basic functions
Function
PEMMXU
RESCMMXU
VMMXU
RESVMMXU
VAMMXU
3.24.3.2
Length of record
The recording capability is about 7.4 years when one quantity is recorded and
the demand interval is set to 180 minutes. The recording time scales down
proportionally when a shorter demand time is selected or more quantities are
recorded. The recording lengths in days with different settings used are presented
Table 342
in
overwritten by the newest data.
Table 342: Recording capability in days with different settings
Amount of
quantities
1
2
Table continues on the next page
312
Signal
S_DMD
P_DMD
Q_DMD
PF_DMD
I_DMD_RES
U_DMD_AB
U_DMD_BC
U_DMD_CA
U_DMD_A
U_DMD_B
U_DMD_C
U_DMD_RES
U_DMD
If the data source for the selected quantity is removed, for example, with
Application Configuration in PCM600, the load profile recorder stops
recording it and the previously collected data are cleared.
. When the recording buffer is fully occupied, the oldest data are
1
5
 minute
 minutes
15.2
75.8
151.6
11.4
56.9
113.7
Description
Demand value of apparent power
Demand value of active power
Demand value of reactive power
Demand value of power factor
Demand value of residual current
Demand value of U12 voltage
Demand value of U23 voltage
Demand value of U31 voltage
Demand value of UL1 voltage
Demand value of UL2 voltage
Demand value of UL3 voltage
Demand value of residual voltage
Demand value of phase voltage
Demand interval
10
15
 minutes
 minutes
 minutes
Recording capability in days
227.4
454.9
170.6
341.1
1MRS759142 F
30
60
180
 minutes
 minutes
909.7
2729.2
682.3
2046.9
REX640