1MRS759142 F
4.1.9.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of PHPTUC can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
Figure 236: Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the
The
If in the "3-phase" mode all the phase current values are less than the value of the
Start value setting, the condition is detected and an enable signal is sent to the
timer. This signal is disabled after one or several phase currents have exceeded the
set
If in the "1-phase" mode any of the phase current values are less than the value of
the
timer. This signal is disabled after all the phase currents have exceeded the set
value value of the element.
Level detector 2
This is a low-current detection module that monitors the de-energized condition of
the protected object. The module compares the phase currents (RMS value) to the
Current block value setting. If all the phase current values are less than the Current
block value setting, a signal is sent to block the operation of the timer.
Timer
Once activated, the timer activates the START output and the phase-specific ST_X
output. The time characteristic is according to DT. When the operation timer has
reached the value set by
specific OPR_X output are activated. If the fault disappears before the module
REX640
Technical Manual
I3P
BLOCK
Operation mode setting can be used to select the "3-phase" or "1-phase" mode.
Start value value of the element.
Start value setting, the condition is detected and an enable signal is sent to the
The protection relay does not accept the
Current block value .
Operate delay time , the OPERATE output and the phase
I_A
I_B
Level
detector 1
I_C
Level
detector 2
Protection functions
Operation setting . The
OPERATE
START
OPR_A
Timer
OPR_B
t
OPR_C
ST_A
ST_B
ST_C
Start value setting.
Start value to be smaller than
Start
407