ABB RELION REX640 Technical Manual page 620

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Figure 353: Permissible time-touch voltage characteristics given in standard
IEEE80 (metal-to-metal contact).
• This operation mode can be also used when maximum allowed earthing voltage,
i.e. earth potential rise, vs. operation speed follows a relationship such as 750V/
• Time margin for practical circuit-breaker operate time can be applied with
setting
• START and ST_EF outputs are activated when estimated touch voltage
(considering the effect of settings
exceeds setting
current estimate is validated. Note that
not affect this start condition.
• OPERATE and OP_EF outputs are activated according to time-touch voltage
characteristics given in standard IEEE80 i.e. operate time is inversely
proportional to the estimated touch voltage.
• Reset timer is started if any of the above conditions for START is not anymore
valid. START and ST_EF outputs stay activated until the reset timer expires
(setting
OPERATE and OP_EF outputs are reset immediately i.e. reset delay time is no
longer valid.
• During re-striking/intermittent earth faults, the very high current transient may
result to very fast operation times. In case longer operation during re-striking/
intermittent earth faults is preferred and operation should be based preferably
on counted number of transients, then setting
set to low value, say 20-40 ms. Dedicated intermittent earth-fault protection
functionality based on counted number of transients is described in
4.2.10.5.6 Intermittent earth-fault protection
• Applicable settings are:
Val, CB delay Comp, IEEE multiplier, IDMT stage Min Op Tm, IDMT stage Max Op
Tm, Reset delay time .
According to the standard IEEE80, the values of the permissible touch voltage U
as a function of the fault duration t
For body weight of 50 kg:
620
t [ sec ].
CB delay Comp . Default setting is 0 ms.
Touch Vol Str Val and earth fault is detected and earth-fault
Reset delay time ). After OPERATE output activation, START, ST_EF,
Reduction factor and Enable harmonics )
Ena RF Compensation = "Enable" does
.
Reduction factor, Maximum earthing Ris, Touch Vol Str
are defined as follows:
f
1MRS759142 F
Reset delay time should be
Technical Manual
Chapter
Tp
REX640