Protection functions
Parameter
Values (Range)
R0 zone 1
0.00...3000.00
X0 zone 1
0.00...3000.00
Factor K0 zone 1
0.00...5.00
Factor K0 angle Zn1 -179...180
Min Ris Gnd Rch
0.00...500.00
Zn1
Max Ris Gnd Rch
0.00...500.00
Zn1
Gnd operate Dl Zn1 20...60000
Directional mode
1=Non-directional
Zn2
2=Forward
3=Reverse
Op Mod PP loops
0=False
Zn2
1=True
PP Op delay Mod
0=False
Zn2
1=True
R1 zone 2
0.00...3000.00
X1 zone 2
0.00...3000.00
X1 reverse zone 2
0.00...3000.00
Z1 zone 2
0.01...3000.00
Z1 angle zone 2
15.0...90.0
Z1 reverse zone 2
0.00...3000.00
Min Ris PP Rch Zn2
0.00...100.00
Max Ris PP Rch Zn2 0.00...100.00
PP operate delay
20...60000
Zn2
Op Mod Gnd loops
0=False
Zn2
1=True
Gnd Op Dl mode
0=False
Zn2
1=True
Load Comp zone 2
0=False
1=True
Table continues on the next page
988
Unit
Step
ohm
0.01
ohm
0.01
0.01
deg
1
ohm
0.01
ohm
0.01
ms
1
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
deg
0.1
ohm
0.01
ohm
0.01
ohm
0.01
ms
1
1MRS759142 F
Default
Description
160.00
Zero sequence re-
sistive reach, zone 1
160.00
Zero sequence re-
active reach, zone 1
1.00
Residual compen-
sation factor mag-
nitude, zone 1
0
Residual compen-
sation factor angle,
zone 1
100.00
Minimum resistive
reach of PE-loops,
zone 1
100.00
Maximum resistive
reach of PE-loops,
zone 1
20
Time delay to op-
erate of PE-loops,
zone 1
2=Forward
Directional mode,
zone 2
0=False
Enable PP/3P-loop
measurement, zone
2
1=True
Enable operate tim-
er for PP/3P-loops,
zone 2
40.00
Positive sequence
resistive reach,
zone 2
40.00
Positive sequence
reactive reach, zone
2
40.00
Pos. seq. reactive
reach in rev. dir.,
non-dir. zone 2
56.57
Positive sequence
reach, zone 2
45.0
Positive sequence
line angle, zone 2
56.57
Positive sequence
reach in rev. dir.,
non-dir. zone 2
30.00
Minimum resistive
reach of PP/3P-
loops, zone 2
30.00
Maximum resistive
reach of PP/3P-
loops, zone 2
20
Time delay to oper-
ate of PP/3P-loops,
zone 2
0=False
Enable PE-loop
measurement, zone
2
1=True
Enable operate tim-
er for PE-loops,
zone 2
1=True
Enable load com-
pensation for PE-
loops, zone 2
Technical Manual