ABB RELION REX640 Technical Manual page 921

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.6.1.4
Analog channel configuration
FRPFRQ has one analog group input which must be properly configured.
Table 879: Analog inputs
Input
U3P
There are a few special conditions which must be noted with the configuration.
Table 880: Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.6.1.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of FRPFRQ can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
Figure 514: Functional module diagram
REX640
Technical Manual
See the preprocessing function blocks in this document for the possible
signal sources.
F
U3P
dF/dt
BLOCK
Description
Three-phase voltages
Description
The function requires that at least one phase
or phase-to-phase voltage channel is connec-
ted.
Operation setting. The
Freq>/<
detection
Operate
logic
df/dt
detection
Blocking
logic
Protection functions
OPERATE
OPR_OFRQ
OPR_UFRQ
OPR_FRG
START
ST_OFRQ
ST_UFRQ
ST_FRG
921

Advertisement

Table of Contents
loading

Table of Contents