Protection functions
MAN_RESTORE
Figure 516: Functional module diagram
Underfrequency detection
The underfrequency detection measures the input frequency calculated from the
voltage signal. An underfrequency is detected when the measured frequency drops
below the set value of the
The underfrequency detection module includes a timer with the definite time (DT)
characteristics. Upon detection of underfrequency, operation timer activates the
ST_FRQ output. When the underfrequency timer has reached the value set by
Operate Tm Freq , the OPR_FRQ output is activated if the underfrequency condition
still persists. If the frequency becomes normal before the module operates, the
reset timer is activated. If the reset timer reaches the value set by
the timer resets and the ST_FRQ output is deactivated.
df/dt detection
The df/dt detection measures the input frequency calculated from the voltage
signal and calculates its gradient. A high df/dt condition is detected by comparing
the gradient to the
the frequency gradient decreases at a faster rate than the set value of
df/dt .
930
U3P
BLK_REST
BLOCK
Start value Freq setting.
Start value df/dt setting. The df/dt detection is activated when
Under
frequency
detection
F
dF/dt
df/dt
detection
Load
shedding
control
Restore
detection
Blocking
logic
1MRS759142 F
ST_FRQ
OPR_FRQ
ST_FRG
OPR_FRG
START
OPERATE
ST_REST
RESTORE
Reset delay time ,
Start value
REX640
Technical Manual