1MRS759142 F
MNSPTOC Output signals
Table 771: MNSPTOC Output signals
Name
OPERATE
START
BLK_RESTART
4.4.5.9
MNSPTOC Settings
Table 772: MNSPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
0.01...0.50
Operating curve
5=ANSI Def. Time
type
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
Machine time Mult
5.0...100.0
Operate delay time
100...120000
Table 773: MNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Maximum operate
500000...7200000
time
Minimum operate
100...120000
time
Cooling time
5...7200
Table 774: MNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Current reference
0.30...2.00
Reset delay time
0...60000
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
ms
1000
ms
1
s
1
Unit
Step
xIn
0.01
ms
1
Protection functions
Description
Operate
Start
Overheated machine recon-
nection blocking
Default
Description
0.20
Start value
15=IEC Def. Time
Selection of time
delay curve type
5.0
Machine related
time constant
1000
Operate delay time
Default
Description
1=on
Operation Off / On
1000000
Max operate time
regardless of the
inverse characteris-
tic
100
Minimum operate
time for IDMT
curves
50
Time required to
cool the machine
Default
Description
1.00
Rated current (Ir) of
the machine (used
only in the IDMT)
20
Reset delay time
849