ABB RELION REX640 Technical Manual page 377

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 420: PHPVOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Num of start pha-
1=1 out of 3
ses
2=2 out of 3
3=3 out of 3
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 421: PHPVOC Non group settings (Advanced)
Parameter
Values (Range)
Measurement
1=RMS
mode
2=DFT
3=Peak-to-Peak
Control mode
1=Voltage control
2=Input control
3=Voltage and in-
put Ctl
4=No Volt depend-
ency
Minimum operate
40...60000
time
Reset delay time
0...60000
4.1.3.9
PHPVOC Monitored data
Table 422: PHPVOC Monitored data
Name
Type
START_DUR
FLOAT32
EFF_ST_VAL_A
FLOAT32
EFF_ST_VAL_B
FLOAT32
EFF_ST_VAL_C
FLOAT32
PHPVOC
Enum
REX640
Technical Manual
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
Unit
Step
ms
1
ms
1
Values (Range)
0.00...100.00
0.00...50.00
0.00...50.00
0.00...50.00
1=on
2=blocked
3=test
4=test/blocked
Protection functions
Default
1=on
1=1 out of 3
28.2000
0.1217
2.00
29.10
1.0
Default
2=DFT
1=Voltage control
40
20
Unit
Description
%
Ratio of start time / op-
erate time
xIn
Effective start value for
phase A
xIn
Effective start value for
phase B
xIn
Effective start value for
phase C
Status
Description
Operation Off / On
Number of phases
required for oper-
ate activation
Parameter A for
customer program-
mable curve
Parameter B for
customer program-
mable curve
Parameter C for
customer program-
mable curve
Parameter D for
customer program-
mable curve
Parameter E for
customer program-
mable curve
Description
Selects used meas-
urement mode
Type of control
Minimum operate
time for IDMT
curves
Reset delay time
377