1MRS759142 F
Module
COM1005
BIO1001/
BIO1003
BIO1002/
BIO1004
RTD1001
RTD1002
AIM1001
AIM1002
SIM1901
SIM1902
PSM1001
PSM1002
PSM1003
PO = Power Output
SPO = Static Power Output
The relay has a nonvolatile memory which does not need any periodical
maintenance. The nonvolatile memory stores all events, recordings and logs to a
memory which retains data if the relay loses its auxiliary supply.
2.3
Local HMI
The LHMI is used for setting, monitoring and controlling the protection relay and
the related process. It comprises a 7-inch color screen with capacitive touch sensing
and a Home button at the bottom of the LHMI.
REX640
Technical Manual
Description
1 × RJ-45 (LHMI port) + 2 × LC + 1 × LD-SFP + 1 × RS-485/IRIG-B + 1 × FO
UART
14 × BI + 8 × SO
6 × SPO + 2 × SPO (TCS) + 9 × BI
10 × RTD channels + 2 × mA channels (input/output)
3 × RTD channels + 6 × mA channels (input/output) + 12 x BI
4 × CT + 1 × CT (sensitive, for residual current only) + 5 × VT
6 × CT + 4 × VT
3 × combi sensor inputs (RJ-45) + 1 × CT (sensitive, for residual current
only) + 1 × VT
3 × combi sensor inputs (RJ-45) + 1 × CT (sensitive, for residual current
only) + 1 × VT
24...60 VDC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
48...250 VDC / 100...240 VAC, 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
110/125 VDC (77...150 VDC), 3 × PO (TCS) + 2 × PO + 3 × SO + 2 × SSO
The LHMI must be paired with the protection relay to enable all the
functionalities in it. See the operation manual for the pairing procedure.
The LHMI is an accessory for the relay which is fully operational even
without the LHMI.
SO = Signal Output
SSO = Static Signal Output
REX640 overview
45