Real Less Than Or Equal Comparator Ler - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
3.22.7.3
Signals
Table 327: GER Input signals
Name
REAL_IN1
REAL_IN2
TOLR
Table 328: GER Output signals
Name
OUT
3.22.8

Real less than or equal comparator LER

3.22.8.1
Function block
Figure 182: Function block
3.22.8.2
Functionality
The real less than or equal comparator function LER compares real input REAL_IN1
with the real input REAL_IN2 and activates the binary output OUT if REAL_IN1 is
equal to or less than REAL_IN2 + TOLR or less than REAL_IN2 input. That is, if
REAL_IN1 ≤ (REAL_IN2 + TOLR) or REAL_IN1 < (REAL_IN2), OUT = 1, else OUT = 0.
306
GER function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
closely varying values.
Type
FLOAT32
FLOAT32
FLOAT32
Type
BOOLEAN
LER function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
closely varying values.
Default
Description
0
Real input 1
0
Real input 2
0
Tolerance for compar-
ison
Description
Output value
1MRS759142 F
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents