1MRS759142 F
Parameter
Values (Range)
Max reverse angle
0...180
Min forward angle
0...180
Min reverse angle
0...180
Voltage start value
0.010...1.000
Table 544: DEFLPDEF Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Enable voltage limit 0=False
1=True
Table 545: DEFLPDEF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 546: DEFLPDEF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum operate
50...60000
time
Allow Non Dir
0=False
1=True
Measurement
1=RMS
mode
Table continues on the next page
REX640
Technical Manual
Unit
Step
deg
1
deg
1
deg
1
xUn
0.001
Unit
Step
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
Unit
Step
ms
1
ms
1
Protection functions
Default
Description
80
Maximum phase
angle in reverse di-
rection
80
Minimum phase an-
gle in forward di-
rection
80
Minimum phase an-
gle in reverse direc-
tion
0.010
Voltage start value
Default
Description
1=Immediate
Selection of reset
curve type
1=Phase angle
Operation criteria
1=True
Enable voltage limit
Default
Description
1=on
Operation Off / On
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
29.10
Parameter D for
customer program-
mable curve
1.0
Parameter E for
customer program-
mable curve
Default
Description
20
Reset delay time
50
Minimum operate
time for IDMT
curves
0=False
Allows prot activa-
tion as non-dir
when dir info is in-
valid
2=DFT
Selects used meas-
urement mode
477